6-30KV Single-Core Armoured Power Cable (AWA)
Application
IEC 60502-2 single-core AWA cable (6kV to 30kV) for power stations, substations, and industrial plants requiring mechanical protection in single-core AC circuits. Non-magnetic aluminum wire armor eliminates eddy current losses. Installation: direct burial, duct, or tray.
Core Strengths
Steel armor on single-core AC creates eddy currents, causing overheating and energy loss. Our non-magnetic AWA eliminates losses. Lightweight, corrosion-resistant. CE/TÜV/ISO. Factory direct.
Standard
IEC60502, SANS 1339, BS 6622, AS/NZS1429.1, NFC 33226, CSA C 68.5, ICEA S 93-639 , ICEA S 94-649
Construction
Conductor: Stranded copper (class 2)
Conductor screen: Semiconductive layer
Insulation: XLPE (cross-linked polyethylene)
Insulation screen: Semiconductive layer
Copper tape screen: Helically applied copper tape
Inner covering: PVC or PE bedding
Armor: Aluminum wire (AWA – non‑magnetic)
Outer sheath: PVC or PE (type ST2)
Features
Rated voltage: 6kV to 30kV (Uo/U up to 18/30kV)
XLPE insulation – 90°C continuous, 250°C short‑circuit
Non‑magnetic aluminum wire armor – eliminates eddy current losses in single‑core AC circuits
Copper tape screen – uniform electric field, corona suppression, fault return path
Lightweight and corrosion‑resistant armor
Ideal for power stations, substations, industrial plants
Installation: direct burial, ducts, cable trays, or aerial (with proper support)
100% factory tested to IEC 60502‑2
Product Data Sheet
| Insulation, Metallic shield Dimension | |||||
| Rated Circuit Voltage, Phase-to-Phase | Conductor Size | XLPE/TRXLPE Insulation Nominal Thickness | Metal Screen | ||
| 100 Percent Level | 133 Percent Level | 173 Percent Level | Copper Tape | ||
| V | AWG/kcmil | mm | mm | mm | mm |
| 2001-5000 | 8-1000 | 2.3 | 2.3 | 3.6 | 0.06 |
| 1001-3000 | 3.6 | 3.6 | 3.6 | 0.06 | |
| 5001-8000 | 6-1000 | 2.9 | 3.6 | 4.4 | 0.06 |
| 1001-3000 | 4.4 | 4.4 | 5.6 | 0.06 | |
| 8001-15000 | 2-1000 | 4.4 | 5.6 | 6.6 | 0.06 |
| 1001-3000 | 5.6 | 5.6 | 6.6 | 0.06 | |
| 15001-25000 | 1-3000 | 6.6 | 8.1 | 10.7 | 0.06 |
| 25001-28000 | 1-3000 | 7.1 | 8.8 | 11.3 | 0.06 |
| 28001-35000 | 1/0-3000 | 8.8 | 10.7 | 14.7 | 0.06 |
| 35001-46000 | 4/0-3000 | 11.3 | 14.7 | 19.1 | 0.06 |
| Concentric Neutral Wire Size | |||
| AWG Size | Nominal Diameter | Nominal Area | |
| mils | mm | (kcmil) | |
| 16 | 50.8 | 1.29 | 2.58 |
| 14 | 64.1 | 1.63 | 4.11 |
| 12 | 80.8 | 2.05 | 6.53 |
| 10 | 101.9 | 2.59 | 10.38 |
| 9 | 114.4 | 2.91 | 13.09 |
| 8 | 128.5 | 3.26 | 16.51 |
| Full Neutral Concentric Copper Conductor | ||||||
| Conductor Size AWG/kcmil | Concentric Conductor Minimum Number of Wires | |||||
| Copper | Aluminum | 16AWG | 14AWG | 12AWG | 10AWG | 9AWG |
| … | 4 | 10* | 6 | … | … | … |
| 4 | 2 | 16* | 10 | … | … | … |
| 3 | 1 | 20* | 13 | … | … | … |
| 2 | 1/0 | 26* | 16 | 10* | … | … |
| 1 | 2/0 | … | 20* | 13 | … | … |
| 1/0 | 3/0 | … | 25* | 16 | 10* | … |
| 2/0 | 4/0 | … | 32* | 20* | 13 | 10* |
| 3/0 | 250 | … | … | 25* | 16 | 13* |
| 4/0 | 350 | … | … | 32* | 20* | 16 |
| One-third Neutral Concentric Copper Conductor | |||||||
| Conductor Size | Concentric Conductor Minimum Number of Wires | ||||||
| AWG/kcmil | |||||||
| Copper | Aluminum | 16AWG | 14AWG | 12AWG | 10AWG | 9AWG | 8AWG |
| 2 | 1/0 | 9 | 6 | … | … | … | … |
| 1 | 2/0 | 11 | 7 | … | … | … | … |
| 1/0 | 3/0 | 14 | 9 | 6* | … | … | … |
| 4/0 | 17 | 11 | 7* | … | … | … | |
| 2/0 | 18 | 11 | 7* | … | … | … | |
| 250 | 20 | 13 | 8* | … | … | … | |
| 3/0 | 22 | 14 | 9* | 6* | … | … | |
| 4/0 | 350 | 28* | 18 | 11* | 7* | 6* | … |
| 250 | … | 21 | 13* | 9* | 7* | … | |
| 500 | … | 25* | 16 | 10* | 8* | 7* | |
| 350 | … | 29* | 18 | 12* | 9* | 8* | |
| 600 | … | 30* | 19 | 12* | 10* | 8* | |
| 750 | … | … | 24 | 15* | 12* | 10* | |
| 500 | … | … | 26* | 17 | 13* | 10* | |
| 600 | 1000 | … | … | 31* | 20 | 16* | 13* |
| 650 | … | … | 34* | 21 | 17* | 14* | |
| 750 | 1250 | … | … | … | 25* | 20 | 16* |
| 1500 | … | … | … | 30* | 24 | 19* | |
| 1000 | … | … | … | 32* | 26* | 21 | |
| Thickness of bedding and size of armor wire | ||
| Calculated Dia. of cable under bedding | Min. thickness of bedding | Nominal size of armor wire |
| mm | mm | mm |
| 0-19.05 | 1.14 | 2.11 |
| 19.08-25.40 | 1.65 | 2.77 |
| 25.43-43.18 | 2.03 | 3.4 |
| 43.21-63.50 | 2.03 | 4.19 |
| 63.53 & larger | 2.41 | 5.16 |